V10/V9 series Operation Troubles HKFAQ000029

date: 2017/9/13

Alarms are not saved in the alarm history as specified for [Number of Data to Save] in the alarm server settings.

 

<Cause>

The setting for [System Setting] -> [Alarm Server] -> [Data Output Setting] -> [Number of Data to Save] is small.

 

<Solution>

Increase the setting for [Number of Data to Save].
If the display mode of the alarm part is "alarm history" or "event history", each occurrence and each reset is counted as one data.
Consequently, to keep one error bit change as historical data, "2" should be set at minimum.

V9series|Alarms_are_not_saved_in_the_alarm_history_as_specified_for_[Number_of_Data_to_Save]_in_the_alarm_server_settings.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • Messages are not displayed in the alarm tracking display.
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
  • » 有关产品
  • » 有关销售
  • » 目录请求
  • » RoHS依据

MONITOUCH

产品阵容
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
支持 »
  • 下载
  • 咨询
  • 推荐的相关机器
代理店 »
  • 国外代理店
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved