V10/V9 series Error HKFAQ000002

date: 2024/11/5

Communication Error "Error code received"

The "error code" in this message indicates errors occurring on the connected device side. Frequently occurring errors are: the PLC device memory address specified by the V series does not exist on the connected device or is out of the available range. Please refer to the following sites for list of frequently occurring error codes:

  • For Mitsubishi Electric and Fuji Electric PLC devices, click here.
  • For other PLC devices, click here.
    * For information about manufacturers or error codes not listed, refer to the relevant connection manuals.

 

[In cases where the error occurs immediately after the V series has started to run]

A PLC device memory address specified for a setting item used on all screens, such as for control area, device memory for backlight and buzzer control, alarm server, logging server, scheduler function, event timer macro, etc., may be the cause of the error.
Check if the specified PLC device memory address is out of range or illegal.

 

[In cases where the error occurs only with a specific screen]

A PLC device memory address specified for the screen with which the error is occurring may be the cause of the error.
Check if the specified PLC device memory address is out of range or illegal.

 

Depending on the setting for [Comm. Error Handling], the error display on the V series may vary.
  [Comm. Error Handling] can be configured as below.

 

Setting location: V-SFT editor [System Setting] -> [Hardware Setting] -> [PLC Properties]

 

  • "Comm. Error Handling: Stop"V9series|Communication Error Error code received

  • "Comm. Error Handling: Continue"V9series|Communication Error Error code received

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • I want to connect to MICREX-SX but "Communication Error: Error Code received " occurs.
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
  • » 有关产品
  • » 有关销售
  • » 目录请求
  • » RoHS依据

MONITOUCH

产品阵容
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
支持 »
  • 下载
  • 咨询
  • 推荐的相关机器
代理店 »
  • 国外代理店
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved