富士电机(中国)有限公司
全球站点
Hakko Electronics (China)
Select Region
  • Global
  • Europe
  • Japan
  • China
  • Asia
    • Taiwan
    • Korea
Print
Font Size
  • Small
  • Medium
  • Large
  • 主页
  • 产品信息
  • 公司信息
  • » 产品信息
  • » 支持
  • » 代理店
  1. 主页 >
  2. 常见问题
V8/TS2060 series Questions about HKFAQ000179

date: 2021/7/28

How to use a storage device with minimal concern for its life or other limitations

The number of the storage device write times can be reduced as described below.

[TS/V8]

Increase the number of sampling times from the primary storage target in the buffering area.
By increasing the number of sampling times, the number of the storage device write times can be reduced.

 

Setting location:
[System Setting] → [Buffering Area Setting] → [Data Output Settings] tab → [Primary storage target] → [Number of Data to Save]

 

Storage timing to the storage device (secondary storage target)

  • When MONITOUCH mode is switched from RUN to STOP
  • When the [Storage Removal] switch is pressed
  • When the CF card cover is opened (V8)
  • When the medium of the primary storage target becomes full
  • When the macro command "SMPL_SAVE", "SMPL_CSV", "SMPL_CSV2", "SMPLCSV_BAK", "SMPLCSV_BAK2" or "SMPL_BAK" is executed
  • When MONITOUCH is turned ON with [Primary storage target: SRAM]
  • When the [Function: Reset] switch is pressed
  • When the "R: Reset" bit in sampling control device memory is ON

 

[V7 series]

Use the cache function.
The cache function saves history data temporarily in cache memory (SRAM/DRAM) and if the cache becomes full, data will be written onto a CF card.

 

Setting location:
Select [System Setting] → [CF Card Setting], and check [Use Cache].
V8series|How to use a CF card with minimal concern for its life or other limitations

Cache memory is provided for each buffer number.

 

Cache capacity
Units: words

DRAM SRAM
 256  256
 512  512
 768  768
 1024  1024
 1280  1280
 1536  1536
 1792  1792
 2048  2048 (built-in SRAM upper limit)
 4K  4K (with SRAM cassette used)
   8K (with SRAM cassette used)
   16K (with SRAM cassette used)

 

Storage timing to the CF card

  • When the specified cache is full
  • When [No. of Samples] specified in the [Buffering Area Setting] dialog is reached
  • When the macro command "SMPL_SAVE", "SMPL_CSV", or "SMPLCSV_BAK" is executed
  • When the mode is switched from RUN to STOP
  • When the [Function: Reset] switch in sampling mode is pressed
  • When the "R: Reset" bit in sampling control memory is ON

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
  • » 有关产品
  • » 有关销售
  • » 目录请求
  • » RoHS依据

MONITOUCH

产品阵容
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
支持 »
  • 下载
  • 咨询
  • 推荐的相关机器
代理店 »
  • 国外代理店
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved