date: 2025/1/15

The V series does not switch from the RUN screen to Local mode.

Click here for the method for switching to Local mode.

 

[If the switch menu is not displayed when the [SYSTEM] switch is pressed]

<Cause>

Advanced Models

  • Any of the following parts are placed in the corners of the screen.
    Switches, data display parts with switches, display areas, slider switches, scroll bars, and table data display parts
  • The display area of a scrolling message is in a corner.

 

Standard/Lite Models

The [SYSTEM] switch is disabled.

 

<Solution>

Advanced Models
Press a corner where the items given above are not placed.
If items are placed in all four corners of the screen, switch the screen to one that has open corners and perform the procedure to display the system menu.

 

Standard/Lite Models
Press the following two switches at the same time for the time specified for [Mode Change Delay Time] (max. 30 seconds). The change-over time is set in the screen data.

  • Models other than V9060iTD
    [SYSTEM] switch and [F7] switch
  • V9060iTD
    [SYSTEM] switch and [F5] switch

 

The change-over time setting can be viewed in the following location.
Setting location: V-SFT-6 editor [System Setting] -> [Unit Setting] -> [System/Mode Switch]

 

[The [Local] switch is not displayed on the system menu] (Standard/Lite models)

<Cause>

[Mode Switch Prohibited] is selected.

 

<Solution>

Press the following two switches at the same time for the time specified for [Mode Change Delay Time] (max. 30 seconds). The change-over time is set in the screen data.

  • Models other than V9060iTD
    [F1] switch and [F7] switch
  • V9060iTD
    [F1] switch and [F5] switch

 

The change-over time setting can be viewed in the following location.
Setting location: V-SFT-6 editor [System Setting] -> [Unit Setting] -> [System/Mode Switch]

       

 

[When the V series does not switch to Local mode even after pressing the [Local] switch on the system menu]

<Cause>

The [Mode Change Delay Time] is specified in the screen data.

 

<Solution>

Press the [Local] switch on the system menu for the time specified for [Mode Change Delay Time] (max. 30 seconds).

 

The change-over time setting can be viewed in the following location.
Setting location: V-SFT-6 editor [System Setting] -> [Unit Setting] -> [System/Mode Switch]

       

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
  • » 有关产品
  • » 有关销售
  • » 目录请求
  • » RoHS依据

MONITOUCH

产品阵容
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
支持 »
  • 下载
  • 咨询
  • 推荐的相关机器
代理店 »
  • 国外代理店
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved